Section 2: Installation
Note:
No module can be more than 1000 ft / 305 m (in wire length) from the panel.
Do not use shielded wire for
Corbus wiring.
Figure 2-19 Corbus wiring
Module (A) is wired correctly as it is within 1000 ft / 305 m of the panel, in wire distance. Module (B) is wired correctly as it is
within 1000 ft / 305 m of the panel, in wire distance. Module (C) is NOT wired correctly as it is farther than 1000 ft / 305 m
from the panel. For models that require more than 1000 ft / 305 m from the main panel, a HSM3204CX power supply/Corbus
extender can be used.
Current ratings
In order for the system to operate properly, the power output of the alarm controller and power supply modules cannot be
exceeded. Use the following data to ensure that the available current is not exceeded.
Table 2-2 System output ratings
Device
Output Rating (12 V DC)
HS3032
HS3128
HS3248
AUX/
Corbus:
2 A. Subtract the listed rating for each keypad, expansion module and accessory connected to AUX or Corbus. At least
100 mA must be reserved for the Corbus.
BELL:
700 mA continuous rating. 2 A. short term. Available only with standby battery connected. DO NOT exceed the 700 mA
load for UL/ULC or EN certified applications.
HSM3350
AUX1:
AUX2:
3 A. Subtract the listed rating for each keypad, expansion module and accessory connected to AUX.
HSM3408
AUX:
500 mA. Continuous rating. Subtract for each device connected. Subtract the total load on this terminal from the alarm
panel AUX/Corbus output.
HSM3204CX AUX/
Corbus:
2 A. Continuous rating. Subtract for each device connected.
HSM2208
AUX:
250 mA. Continuous rating. Subtract for each device connected. Subtract the total load on this terminal from the alarm
panel AUX/Corbus output.
HSM2108
AUX:
100 mA. Subtract for each device connected. Subtract the total load on this terminal from the panel AUX/Corbus output.