Appendix 5: Regulatory approvals
Notes
l
Programming at installation may be subordinate to other UL requirements for the intended application.
l
Cross zones have the ability to individually protect the intended area (e.g. motion detectors which overlap).
l
Cross zoning is not recommended for line security Installations nor is it to be implemented on exit/entry zones.
l
This control panel has a communication delay of 30 seconds. It can be removed or increased up to 45 seconds by
the end user with installer consultation.
l
The system shall be installed with the sounding device activated and the communicator enabled for transmission
using SIA or CID format.
l
ULC commercial burglary installations require DEOL resistors.
Table 5-1 SIA quick reference
SIA Feature Programming Section
Comments
Range/Default Requirement
Exit Time
[005]>[001], option 3
Access to Entry and Exit delays and Bell Time Out for the system.
Range:45-
255 seconds
Default: 60
sec.
Required
(programmable)
Exit Delay Restart
[018], option 7
Opening a Delay zone door after it has already been opened and
closed during an exit delay restarts the exit delay timer.
Default:
Enabled
Required
Auto Stay Arm on Un-vacated
Premises
[001]>[001]-[248] Zone type 05, 06,09
Function key: Forces the system to arm in Stay mode if the occupant
does not exit the premises after pressing the Away function key.
If no exit after
full arm
Default:
Enabled
Required
Exit Time and Progress
Annunciation/Disable or Remote
Arming
[861]>[001]-[005], option 4
System times and audible exit beeps can be disabled when using the
wireless key to stay arm the system. When away arming, audible exit
beeps can not be disabled.
For remote arming (using keyfob), it is possible to program the instant
stay arm (no exit delay). By default this option is OFF.
When arming/disarming with keyfob the bell squawk option shall be
enabled.
The Bell shall be tested daily. Alternate option is to have bell squawk
enabled for arming/disarming
Default:
Enabled
Allowed
Entry delay(s)
[005]>[001]-[008], options 1 and 2
Access to entry and exit delays and bell time out for the system
Note: Combined entry delay and communications delay (abort
window) shall not exceed 60s.
Range: 30
sec. to 4 min.
Default: 30
sec.
Required
(programmable)
Abort Window for Non-Fire zones
[002]>[001]-[248], option 7 ON
Access to zone attributes, i.e., swinger shutdown, transmission delay
and cross zone. May be disabled by zone or zone type.
Default:
Enabled
Required
Abort Window Time - for Non-Fire
zones
[377]>[002], option 1
Access to the programmable delay before communicating alarms
Note: Combined entry delay and communications delay (abort
window) shall not exceed 60 seconds.
Range: 00 - 45
sec.
Default: 30
sees
Required
(programmable)
Abort Annunciation
An audible tone is generated when an alarm is aborted during the
abort window.
Hard-coded
ON
Required
Duress Feature
[*][5]> master code> user 2-95> 5> 2
When this feature is enabled, selected user codes send a duress
reporting code to the central station when used to perform any
function on the system. Section [019], option [6] must be enabled.
Default: N
Required
Cancel Window
[377]>[002], option 6
Access to the communications cancel window. Minimum duration
must be 5 minutes.
Range: 005-
255
Default: 005
Cancel Annunciation
[308]>[001], option 8
Access to the reporting code for Alarm Canceled.
A Cancel was
transmitted
Default:
Enabled
Required
- 271 -