Section 5: Programming
Note:
The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this
zone type is 5k6, the alarm state is short and the trouble state is open. For use with normally open contacts.
042
–
24-Hour Holdup
Instant alarm when activated, silent alarm at default.
Note:
Not for use in UL listed installations.
043
–
24-Hour Panic
Instant alarm when activated, audible alarm at default.
045
–
24-Hour Heat
Instant alarm when activated, audible alarm at default.
046
–
24-Hour Medical
Instant alarm when activated, audible alarm at default.
047
–
24-Hour Emergency
Instant alarm when activated, audible alarm at default.
048
–
24-Hour Sprinkler
Instant alarm when activated, audible alarm at default.
049
–
24-Hour Flood
Instant alarm when activated, audible alarm at default.
051
–
24-Hour Latching Tamper
Instant alarm when activated, audible alarm at default. The alarm system cannot be armed until Installer Programming is
entered after the zone is restored.
052
–
24-Hour Non-Alarm
This zone is active at all times but does not cause an alarm. Zone attributes such as Zone Bypassing and Door Chime affect
the functionality of this zone. This zone type can also be assigned to a temperature sensor if indoor/outdoor temperature dis-
play is required without temperature warnings or alarm conditions.
056
–
24 Hour High Temperature
This zone type is used with wireless temperature sensors and is activated when the temperature rises above a programmed
threshold (set in section [804][xxx][019-020]). Instant alarm when activated, audible alarm at default. This zone type gen-
erates an alarm when the system is armed or disarmed.
Note:
This zone type cannot be used on hardwired zones. The temperature threshold includes a 3 °C (5-6 °F) difference
between a given state and its restored condition. For example, an alarm at 6 °C is restored at 3°C (High temperature) or 9°C
(Low temperature), depending upon the zone type selected.
The zone type for wireless temperature sensors must be 24 Hour High/Low Temperature in order for the sensor to operate
properly.
057
–
24-Hour Low Temperature
This zone type is used with wireless temperature sensors and is activated when the temperature drops below a programmed
threshold (set in section [804][xxx][019-020]). Instant alarm when activated, audible alarm at default. This zone type gen-
erates an alarm when the system is armed or disarmed.
Note:
This zone type cannot be used on hardwired zones.
060
–
24-Hour Non-Latching Tamper
This zone is always active and reports a tamper condition with no audible alarm when opened or tamper/faulted.
061 - 24-Hour Masking
This zone is active 24 hours in either the armed or the disarmed state. This zone type does not generate an alarm, and does
not log in the Alarm Memory. This zone type generates a Masking Trouble on the system.
Note:
This zone operates in SEOL only.
066
–
Momentary Keyswitch Arm
Often used with a keyswitch module*, turning the key alternately arms and disarms the system and silences the alarms.
Tampers and faults only initiate their respective trouble sequence. The keypad gives no indication when this zone type is
activated.