Total current measurement
If the current measurement is done via two current
transformers, the overall transformation ratio of
the current transformers must be programmed into
the UMG 96RM-PN.
Example: The current is measured via two current
transformers. Both current transformers have a
transformation ratio of 1000/5A. The summation
measurement is performed using a total current
transformer 5+5/5A.
The UMG 96RM-PN must then be setup as follows:
Primary current:
1000A + 1000A = 2000A
Secondary current:
5A
Fig. Current measurement via a total current transformer
(example).