82
UMG 96RM-PN
Comparators and threshold value monitoring
Two comparator groups (1 - 2), each with 3 comparators
(A - C) are available to monitor threshold values.
The results of Comparators A to C can be combined with
the AND/OR operators.
The combination result of Comparator group 1 can be
assigned to Digital output 1 and the combination result
of Comparator group 2 can be assigned to Digital output
2.
Additionally, the function "Flash display" can also
be assigned to each comparator group, whereby
the backlight of the screen alternates between maximum
and minimum brightness when a comparator output is
active.
Fig.: GridVis software, configuration menu
We recommend configuring the comparator
and threshold value monitoring settings in
GridVis.
C
The comparator or combination results
cannot be assigned to the digital outputs of
Group 2!
Digital input values of group 2 and analogue
input values ( residual current and tempe-
rature monitoring ) as well as current moni-
toring input I4
cannot be used by compa-
rators.