58
UMG 96RM-PN
Averaging method
The used exponential averaging method achieves at
least 95% of the measured value after the set averaging
time.
Min. and max. values
All measured values are measured and calculated every
10/12 periods. Min. and max. values are determined for
most measured values.
The min. value is the lowest measured value measured
since the last time the values were cleared. The min.
value is the lowest value measured since the last time
the values were cleared. All min. and max. values are
compared with the associated measured values, and
overwritten if the value is under the min. value or over
the max. value.
The min. and max. values are stored every 5 minutes to
an EEPROM without the date and time. This means that,
if there is failure of the supply voltage, only the min. and
max. values for the last 5 minutes can be lost.
Clearing the min. and max. values (addr.506)
If "001" is written to address 506, all min. and max.
values are cleared simultaneously.
Parameters
Mean value
Averages for the current, voltage, and power measured
values are calculated over an adjustable period.
The averages are identified by a bar over the top of
the measured value.
The averaging time can be selected from a list of 9 fixed
averaging times.
Current averaging time (addr. 040)
Power averaging time (addr. 041)
Voltage averaging time (addr. 042)
Setting
Averaging time/Sec.
0
5
1
10
2
15
3
30
4
60
5
300
6
480 (factory setting)
7
600
8
900
Содержание UMG 96 RM-PN
Страница 25: ...25 UMG 96RM PN c Attention The UMG96RM is only approved for measuring current with a current transformer...
Страница 116: ...116 UMG 96RM PN Dimension diagrams All dimensions in mm Rear view View from below 110 5 91 5 91 5 110 5...
Страница 117: ...117 UMG 96RM PN 92 0 8 92 0 8 Side view Cut out size ca 90 72 96 6 57 78 91 5 104 Depth without plug 91 5 approx 90...
Страница 123: ...123 UMG 96RM PN...
Страница 128: ...128 UMG 96RM PN...