95
UMG 96RM-PN
Possible fault
Cause
Remedy
Effective power too high or too low.
The programmed CT ratio is incorrect.
Read out and program the CT ratio at the current
transformer
The current circuit is assigned to the wrong
voltage circuit.
Check connection and correct if necessary.
The programmed voltage transformer ratio is
incorrect.
Read out and program the voltage transformer
ratio at the voltage transformer.
An output is not responding.
The output was incorrectly programmed.
Check the settings and correct if necessary.
The output was incorrectly connected.
Check connection and correct if necessary.
"EEE" on the display
See error messages.
No connection with the device.
RS485
- Device address is incorrect
- Different bus speeds (baud rate)
- Wrong protocol
- Termination missing
- Adjust the device address
- Adjust speed (baud rate)
- Select the correct protocol
- Terminate bus with termination resistor
Ethernet / ProfiNet
- IP Device address is incorrect.
- Adjust IP device address.
Device still does not work despite
the above measures.
Device defective.
Send the device to the manufacturer for
inspection and testing along with an accurate
fault description.
Содержание UMG 96 RM-PN
Страница 25: ...25 UMG 96RM PN c Attention The UMG96RM is only approved for measuring current with a current transformer...
Страница 116: ...116 UMG 96RM PN Dimension diagrams All dimensions in mm Rear view View from below 110 5 91 5 91 5 110 5...
Страница 117: ...117 UMG 96RM PN 92 0 8 92 0 8 Side view Cut out size ca 90 72 96 6 57 78 91 5 104 Depth without plug 91 5 approx 90...
Страница 123: ...123 UMG 96RM PN...
Страница 128: ...128 UMG 96RM PN...