78
UMG 96RM-PN
Source selection (addr. 200, 202):
Enter here which source the measured value will supply
that should be output on the digital output.
Selectable sources:
• Comparator group
• Pulse
• External source
Fig.: Block diagram; example of Digital output 1 as a pulse output.
Digital
output 1
13
14
Selection
of source
Pulse
Addr. 100 = 874 (address of Psum3)
Addr. 106 = 5 (50 ms)
Addr. 102 = 1000 (Wh/pulse)
Addr. 200 =1
0/1
UMG 96RM-PN
0/1
Inverter
Addr. 201=0 (not inverted)
Addr. 201=1 (inverted)
0/1
Addr. 608 =0
Status of
Digital output 1
Display
K1
K2
Measured value selection (addr. 100, 101):
Enter the address here for the power value which should
be output as the effective pulse. See Table 2.