UMG 96RM-PN
RS485 device address (addr. 000)
If multiple devices are connected together via the RS485
interface, then a Master device is only able to distinguish
between these devices based on their device address.
Therefore each device on a network must have a different
device address. Addresses can be set in the range from
1 to 247.
C
The setting range for the device address is
between 0 and 255. The values 0 and 248
to 255 are reserved and must not be used.
Setting
Baud rate
0
9.6 kbps
1
19.2 kbps
2
38.4 kbps
3
57.6 kbps
4
115.2 kbps (factory setting)
RS485 baud rate (addr. 001)
A common baud rate can be set for the RS485 interfaces.
A common baud rate must be selected in the network.
Address 003 can be used to set the number of stop bits
(0=1Bit, 1=2Bits). Data Bits (8) are preset to fixed values.