51
UMG 96RM-PN
Programming the current transformer for I1-I3
Switch to Programming mode:
• Switching to Programming mode is done by pressing
buttons 1 and 2 simultaneously. If a user password
has been set, then the password prompt appears
with "000". The first digit of the user password flashes
and can be modified with button 2. Pressing button 2
selects the next digit (it starts flashing). If the correct
combination of number has been entered or if no user
password was set, you are taken to Programming
mode.
• The symbols for Programming mode "PRG", and for
the current transformer "CT" appear.
• The selection is confirmed with button 1.
• The first digit of the input range for the primary current
flashes.
Enter the current transformer primary current:
• Modify the flashing digit with button 2.
• Use button 1 to select the next number you wish to
modify. The selected digit to be modified flashes. If
the entire number flashes, the decimal point can be
moved with button 2.
Enter the current transformer secondary current:
• Only 1A or 5A can be set as the secondary current.
• Use button 1 to select the secondary current.
• Modify the flashing digit with button 2.
Exit Programming mode:
• Exit Programming mode by pressing button 1 and 2
at the same time.
Содержание UMG 96 RM-PN
Страница 25: ...25 UMG 96RM PN c Attention The UMG96RM is only approved for measuring current with a current transformer...
Страница 116: ...116 UMG 96RM PN Dimension diagrams All dimensions in mm Rear view View from below 110 5 91 5 91 5 110 5...
Страница 117: ...117 UMG 96RM PN 92 0 8 92 0 8 Side view Cut out size ca 90 72 96 6 57 78 91 5 104 Depth without plug 91 5 approx 90...
Страница 123: ...123 UMG 96RM PN...
Страница 128: ...128 UMG 96RM PN...