Cable type
The cable used must be suitable for an environmental
temperature of at least 80°C.
Recommended cable types:
Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)
Unitronic BUS L2/FIP 1x2x0.64 (from Lapp Kabel)
Maximum cable length
1200m at a baud rate of 38.4k.
Screening
Twisted screened cable should be used for connections
via the RS485 interface.
• Earth the screens of all cables that lead to the cabinet
and at the cabinet entry.
• Connect the screens over a generous area and in a
manner that will conduct well, to a low-noise earth.
• Gather the cables mechanically above the earthing
clamp in order to avoid damage due to cable
movements.
• Use suitable cable glands to feed the cables into
the cabinet, for example, armoured conduit couplings.
Fig. Screening procedure at cabinet entry.
Cable
Strain relief
Screen braid of the cable
Earthing clamp
Noiseless ground
C
CAT cables are not suitable for bus
wiring. Use the recommended cable
types for this.