40
UMG 96RM-PN
Input/output byte coding
(Input/output data of the ProfiNet „digital IO“ module)
• If the digital inputs/outputs in group 2 are configured
as inputs, bit-oriented coding of the statuses occurs
(bit 0 to 2). In this case, coding corresponds to the
digital inputs with:
Bit 0 1 2 3 4 5 6 7
Input 3: 1 = signal is present
Input 2: 1 = signal is present
Input 1: 1 = signal is present
• The digital outputs can be controlled by setting the
corresponding bits.
• If, for example, the digital inputs/outputs in group 2
are configured as outputs, bit-oriented coding occurs
within bits 0 to 4:
Bit 0 1 2 3 4 5 6 7
Output 5: 1 = signal set
Output 4: 1 = signal set
Output 3: 1 = signal set
Output 2: 1 = signal set
Output 1: 1 = signal set