99
UMG 96RM-PN
Current measurement I1 - I4
Rated current
5A
Measurement range
0 to 6A
rms
Crest factor
1,98
Resolution
0.1mA (display 0.01A)
Overvoltage category
300V CAT II
Measurement surge voltage
2kV
Power consumption
Approx. 0.2 VA (Ri=5mΩ)
Overload for 1 sec.
120A (sinusoidal)
Sampling rate
21.33 kHz (50Hz), 25.6 kHz (60Hz) for each measurement channel
Residual current monitoring I5 / I6
Rated current
30mA
rms
Measurement range
0 .. 40mA
rms
Triggering current
50
µ
A
Resolution
1
µ
A
Crest factor
1.414 (related to 40mA)
Burden
4 Ohm
Overload for 1 sec.
5A
Sustained overload
1A
Overload for 20 ms
50A
Residual current monitoring
i.a.w. IEC/TR 60755 (2008-01), type A
Type B
Содержание UMG 96 RM-PN
Страница 25: ...25 UMG 96RM PN c Attention The UMG96RM is only approved for measuring current with a current transformer...
Страница 116: ...116 UMG 96RM PN Dimension diagrams All dimensions in mm Rear view View from below 110 5 91 5 91 5 110 5...
Страница 117: ...117 UMG 96RM PN 92 0 8 92 0 8 Side view Cut out size ca 90 72 96 6 57 78 91 5 104 Depth without plug 91 5 approx 90...
Страница 123: ...123 UMG 96RM PN...
Страница 128: ...128 UMG 96RM PN...