Pulse length
The pulse length applies to both pulse outputs and is set
by the software GridVis.
The typical pulse length of S0 pulse is 30ms.
Pulse interval
The pulse interval is at least as large as the selected
pulse length.
The pulse interval depends on the measured power, for
example, and can take hours or days.
Pulse length
10ms .. 10s
Pulse interval
>10ms
The values in the table are based on the minimum pulse
length and the minimum pulse interval for the maximum
number of pulses per hour.
Examples of the maximum possible number of pulses
per hour.
Pulse length
Pulse interval
Max. pulse/h
10 ms
10 ms
180 000 pulse/h
30 ms
30 ms
60 000 pulse/h
50 ms
50 ms
36 000 pulse/h
100 ms
100 ms
18 000 pulse/h
500 ms
500 ms
3600 pulse/h
1 s
1 s
1800 pulse/h
10 s
10 s
180 pulse/h
Measured value selection
When programming with GridVis you
have a selection of work values which are
derived from the power output values.
C
Pulse interval
The pulse interval is proportional to
the power output within the selected
settings.