108
UMG 96RM-E
Address
format
RD/WR
Unit
Note
Adjustment range
Default
45
USHORT
RD/WR
mA
Response threshold of
0 .. 200
5
current measuring I1 .. I3
50
SHORT
RD/WR
-
Password
0 .. 999
0 (No password)
100
SHORT
RD/WR
-
Measured value address,
Digital output 1
0..32000
874
101
SHORT
RD/WR
-
Measured value address,
Digital output 2
0..32000
882
102
FLOAT
RD/WR
Wh
Pulse value,
Digital output 1
-1000000..+1000000 1000
104
FLOAT
RD/WR
Wh
Pulse value,
Digital output 2
-1000000..+1000000 1000
106
SHORT
RD/WR
10ms
Min. pulse length (1=10ms)
Digital output 1/2
1..1000
5 (=50ms)
206
SHORT
RD/WR
s
“Drag indicator” period duration
300..3600
900
207
SHORT
RD/WR
s
“Drag indicator” capture time
1..20
10
208
SHORT
RD/WR
-
Config. Digital input 1
0 .. 2
0
0=
internal synchronisation
1=
external synchronisation (NO)
2=
external synchronisation (NC)
500
SHORT
RD/WR
-
Connector pin assignment, I L1
-3..0..+3
1)
+1
501
SHORT
RD/WR
-
Connector pin assignment, I L2
-3..0..+3
1)
+2
502
SHORT
RD/WR
-
Connector pin assignment, I L3
-3..0..+3
1)
+3
503
SHORT
RD/WR
-
Connector pin assignment, U L1
0..3
1)
1
504
SHORT
RD/WR
-
Connector pin assignment, U L2
0..3
1)
2
505
SHORT
RD/WR
-
Connector pin assignment, U L3
0..3
1)
3
506
SHORT
RD/WR
-
Min- und Reset max. values
0..1
0
507
SHORT
RD/WR
-
Reset energy meter
0..1
0
508
SHORT
RD/WR
-
force EEPROM descr.
0..1
0
Note: Energy values and min-max values are recorded into the EEPROM every 5 minutes.
1)
0 = No measurement of the current or voltage path.
2)
The setting 8 is equal setting 0.
Содержание UMG 96 RM-E
Страница 25: ...25 UMG 96RM E c Caution The UMG96RM is only approved for a current measurement using the current transformer...
Страница 114: ...114 UMG 96RM E Dimension diagrams All dimensions provided in mm Rear view View from below 110 5 91 5...
Страница 115: ...115 UMG 96RM E Side view ca 90 72 96 6 57 78 91 5 104 depth without connector 92 0 8 92 0 8 Cut out size...
Страница 121: ...121 UMG 96RM E...
Страница 126: ...126 UMG 96RM E...