41
UMG 96RM-E
Digital outputs
These outputs are galvanically separated from
the analysis electronics using optocouplers. The digital
outputs have a joint reference.
• The digital outputs of group 1 can switch DC and AC
loads. The digital outputs of group 2 can
not switch
AC loads.
• The digital outputs are
not short-circuit proof.
• Connected cables that are longer than 30m must
be shielded when laid.
• An external auxiliary voltage is required.
• The digital outputs can be used as impulse outputs.
• The digital outputs can be controlled via Modbus.
• The digital outputs can display the results
of comparators.
~
~
Group 2
Group 1
Fig. Connection
digital / pulse outputs
Содержание UMG 96 RM-E
Страница 25: ...25 UMG 96RM E c Caution The UMG96RM is only approved for a current measurement using the current transformer...
Страница 114: ...114 UMG 96RM E Dimension diagrams All dimensions provided in mm Rear view View from below 110 5 91 5...
Страница 115: ...115 UMG 96RM E Side view ca 90 72 96 6 57 78 91 5 104 depth without connector 92 0 8 92 0 8 Cut out size...
Страница 121: ...121 UMG 96RM E...