92
UMG 96RM-E
Overranges
Overranges are displayed as long as they exist
and cannot be acknowledged. An overrange exists
if at least one of the four voltage or current measurement
inputs lies outside their specified measuring range.
The "upwards" arrow indicates the phase where the
overrrange occured. The appropriate error message for
current path I4 is generated as shown below.
The “V” and “A” symbols indicate whether the overrange
occurred in the current or in the voltage path.
I
= 7 Aeff
U
L-N
= 300 V
rms
Overrange limits:
A = current path
V = voltage path
Indication of the phase (L1/
L2/L3) with overrange.
The current phase l4
overranges occur as shown
in the figure below.
Examples
A = current path
Fig.: Indication
of the overrange
in the current path of phase
2 (l2).
Fig.: Indication
of the overrange in voltage
path L3.
V = voltage path
Fig.: Indication
of the overrange in current
path l4
Содержание UMG 96 RM-E
Страница 25: ...25 UMG 96RM E c Caution The UMG96RM is only approved for a current measurement using the current transformer...
Страница 114: ...114 UMG 96RM E Dimension diagrams All dimensions provided in mm Rear view View from below 110 5 91 5...
Страница 115: ...115 UMG 96RM E Side view ca 90 72 96 6 57 78 91 5 104 depth without connector 92 0 8 92 0 8 Cut out size...
Страница 121: ...121 UMG 96RM E...
Страница 126: ...126 UMG 96RM E...