Bus structure
• All devices are connected in a bus structure (line) and
each device has its own address within the bus (also
see programming parameters).
• Up to 32 stations can be interconnected in one
segment.
• The cable is terminated with resistors (bus termination,
120 ohm 1/4 W) at the beginning and end of a segment.
• If there are more than 32 stations, repeaters (line
amplifiers) must be used in order to connect
the individual segments.
• Devices with activated bus termination must
be supplied with power.
• It is recommended to set the master at the end
of a segment.
• The bus is inoperative if the master is replaced with
an activated bus termination.
• The bus can become unstable if the slave is replaced
with an activated bus termination or is dead.
• Devices that are not involved in the bus termination
can be exchanged without making the bus unstable.
• The shield has to be installed continuously and needs
to be broadly and well conducting connected to an
external low voltage (or potential) ground at the end.
Fig. Bus structure
Slave
Slave
Slave
Slave
Slave
Slave
Repeater
Slave
Slave
Slave
Slave
Master
Power supply necessary
Bus terminator on
T
T
T
T
T
Содержание UMG 96 RM-E
Страница 25: ...25 UMG 96RM E c Caution The UMG96RM is only approved for a current measurement using the current transformer...
Страница 114: ...114 UMG 96RM E Dimension diagrams All dimensions provided in mm Rear view View from below 110 5 91 5...
Страница 115: ...115 UMG 96RM E Side view ca 90 72 96 6 57 78 91 5 104 depth without connector 92 0 8 92 0 8 Cut out size...
Страница 121: ...121 UMG 96RM E...
Страница 126: ...126 UMG 96RM E...