106
UMG 96RM-E
Table 1 – Parameter list
Address
format
RD/WR
Unit
Note
Adjustment range
Default
Parameter and modbus address list
The following excerpt of the parameter list provides
the settings that are necessary for the proper operation
of the UMG 96RM-E, such as current transformer
and device addresses. The values in the parameter list
can be set and read.
The excerpt of the measured value list includes
the measured and calculated values, output status data
and recorded values to be read.
C
A complete overview of the parameters and
measured values as well as explanations
regarding the selected measured values
is filed in the document “Modbus Address
List” on the CD or Internet.
C
The addresses contained in the description
can be adjusted directly on the device
in the range from 0 to 800. The address
range above 1000 can only be processed
via modbus!
(*1)
Values 0 and 248 through 255 are reserved and may not be used.
(*2)
The adjustable value of 0 does not produce any useful work values and must not be used.
0
SHORT
RD/WR
-
Device address
0..255
(*1)
1
1
SHORT
RD/WR
kbps
Baud rate (0=9.6kbps, 1=19.2kbps,
0..7
4
2=38.4kbps, 3= 57.6kbps
(5..7 only for
4=115.2kbps)
internal
use)
2
SHORT
RD/WR
-
Modbus Master
0, 1
0
0=Slave, 1=Master (if Ethernet is provided)
3
SHORT
RD/WR
-
Stoppbits
0..3
0
0 = 1 Bit, none parity
1 = 2 Bits, none parity
2 = 1 Bit, even parity
3 = 1 Bit, uneven parity
10
FLOAT
RD/WR
A
Current transformer I1, primary
0..1000000
(*2)
5
12
FLOAT
RD/WR
A
Current transformer l1, sec.
1..5
5
Содержание UMG 96 RM-E
Страница 25: ...25 UMG 96RM E c Caution The UMG96RM is only approved for a current measurement using the current transformer...
Страница 114: ...114 UMG 96RM E Dimension diagrams All dimensions provided in mm Rear view View from below 110 5 91 5...
Страница 115: ...115 UMG 96RM E Side view ca 90 72 96 6 57 78 91 5 104 depth without connector 92 0 8 92 0 8 Cut out size...
Страница 121: ...121 UMG 96RM E...
Страница 126: ...126 UMG 96RM E...