LVLØ Water Temperature Setpoint Hysteresis Input °C
control EIS5
2 Byte
W
9.001
Floating value (°C). Control hysteresis of the 2-step heating/cooling
controller for water temperature from KNX. Setting rule: Small
hysteresis leads to small fluctuations, but frequent switching.
Large hysteresis leads to big fluctuations, but infrequent switching.
10/2/7
LVLØ Water Temperature Setpoint Hysteresis Output °C
display of
value EIS5
2 Byte
R
9.001
Display actual set point hysteresis temperature.
Floating value (°C) is cyclically sent to bus every 600s.
Group
Address
Data Point Name
Data Point Type
Description
10/2/8
LVLØ Cooling Enable Control (Send 1/0)
control pulse
edge 1/0
1 bit
W
1.001
Actuator to enable/disable water cooling feature. Toggle current
output status when pulse edge telegram (0/1) will be received on
this input. Status feedback will be send when output changes
state.
10/2/9
LVLØ Cooling Status Feedback (0=Disabled;1=Enabled)
display of
status
1 bit
R
1.001
Status feedback of the cooling feature output.
10/2/10
LVLØ 6-Way Valve Control Input
control EIS5
2 Byte
W
7.*
Control input to switch position of "6 WAY VALVE" outputs. To
switch position, send telegram with number of desired valve
position:
1 - position closed
2 - position backwash
3 - position recirculate
4 - position waste
5 - position filter
6 - position rinse
Actual position will be send via status feedback object.
10/2/11
LVLØ 6-Way Valve Status Feedback
display of
value EIS5
2 Byte
R
7.*
Display actual position of "6 WAY VALVE" output. Telegram with
position is sent on change and cyclically every 600s. Position
values:
1 - position closed
2 - position backwash
3 - position recirculate
4 - position waste
5 - position filter
6 - position rinse
10/2/12
LVLØ Pool Mode Control Input
control EIS5
2 Byte
W
7.*
Control actual pool mode. To switch mode, send telegram with
number of desired mode:
1 - in use
2 - closed
3 - winter
NOTE: service mode can be controlled only from device LCD panel
10/2/13
LVLØ Pool Mode Control Output
display of
value EIS5
2 Byte
R
7.*
Display current pool mode via status feedback value. Telegram
with current mode number is sent to bus on change and cyclically
every 600s.
1 - pool in use
2 - pool closed
3 - pool winter mode
4 - pool service mode
10/2/14
LVLØ Heating Valve Control (Send 1/0)
control pulse
edge 1/0
1 bit
1.001
Actuator to control "3 WAY VALVE" output. Toggle current output
state (open/closed) when pulse edge telegram (0/1) will be
received on this input. Use this input to control heating valve from
master heating system.
10/2/15
LVLØ Minimum Sensors Sending Interval Input (s)
control of
value EIS5
2 Byte
W
7.005
Control interval for sending measured values (temperatures, CLF,
pH, ORP) to bus. Applies only to sensors.