6.3.3
10/0/x Communication objects for Home screen and statistics section
Group
Address
Data Point Name
Data Point Type
Description
10/0/0
LVLØ Water Temperature Output °C
display of
value EIS5
2 Byte
R
9.001
Display actual water temperature.
Floating value (°C), cyclically send to bus.
10/0/1
LVLØ Outside temperature Input °C
control EIS5
2 Byte
W
9.001
Control outside temperature from KNX
Floating value (°C).
NOTE: Setting via LVLØ mobile app must
Settings>Service>HEATING>outside temperature source is set to
"KNX" option.
10/0/2
LVLØ Outside Temperature Output °C
display of
value EIS5
2 Byte
R
9.001
Display actual outside temperature.
Floating value (°C), cyclically send to bus.
10/0/3
LVLØ Light Control (Send 1/0)
control pulse
edge 1/0
1 bit
W
1.001
Actuator to control "LIGHT" output. Toggle current output status
when pulse edge telegram (0/1) will be received on this input.
Status feedback will be send when output changes state.
10/0/4
LVLØ Light Status Feedback (1=On, 0=Off)
display of
status
1 bit
R
1.001
Status feedback of "LIGHT" output.
10/0/5
LVLØ Pool Cover Control - Open (Send 1/0)
control pulse
edge 1/0
1 bit
W
1.001
Actuator to control "POOL COVER" output. Pool cover will open
when pulse edge (0/1) telegram will be received on this input.
10/0/6
LVLØ Pool Cover Control - Close (Send 1/0)
control pulse
edge 1/0
1 bit
W
1.001
Actuator to control "POOL COVER" output. Pool cover will close
when pulse edge (0/1) telegram will be received on this input.
10/0/7
LVLØ Pool Cover Status Feedback (1=Open, 0=Closed)
display of
status
1 bit
R
1.001
Status feedback of "POOL COVER" output is sent to bus when the
output changes state. Feedback is sent cyclically to bus every 600s.
10/0/8
LVLØ AUX1 Control (Send 1/0)
control pulse
edge 1/0
1 bit
W
1.001
Actuator to control "AUX1" output. Toggle current output status
when pulse edge telegram (0/1) will be received on this input.
Status feedback will be send when output changes state.
10/0/9
LVLØ AUX1 Status Feedback (1=On, 0=Off)
display of
status
1 bit
R
1.001
Status feedback of "AUX1" output.
10/0/10
LVLØ AUX2 Control (Send 1/0)
control pulse
edge 1/0
1 bit
W
1.001
Actuator to control "AUX2" output. Toggle current output status
when pulse edge telegram (0/1) will be received on this input.
Status feedback will be send when output changes state.
10/0/11
LVLØ AUX2 Status Feedback (1=On, 0=Off)
display of
status
1 bit
R
1.001
Status feedback of "AUX2" output.
10/0/12
LVLØ Current Actual pH Output
display of
value EIS5
2 Byte
R
9.*
Display actual pH value.
Floating value is sent to bus on change or cyclically based on
parameter 10/2/15.
10/0/13
LVLØ Current Actual Redox Output mV
display of
value EIS5
2 Byte
R
9.020
Display actual Redox/ORP value in mV (-2000 +2000).
Value is sent to bus on change or cyclically based on parameter
10/2/15.
10/0/14
LVLØ Current Actual Free Chlorine Output mg/l
display of
value EIS5
2 Byte
R
9.*
Display actual CLF (Free chlorine) value in mg/l (ppm).
Floating value is sent to bus on change or cyclically based on
parameter 10/2/15.
10/0/15
LVLØ Current External System Temperature Output °C
display of
value EIS5
2 Byte
R
9.001
Display actual temperature of external heating/cooling system.
Floating value (°C) is cyclically sent to bus.
6.3.4
10/1/x Communication objects for Dashboard section
Group
Address
Data Point Name
Data Point Type
Description
10/1/0
LVLØ Service Required Status Feedback (1=Required, 0=OK)
display of
status
1 bit
R
1.001
Summarized status feedback object to display if service
intervention on pool is required. Telegram is sent cyclically to bus
every 600s.
10/1/1
LVLØ Service Area Status Feedback (0=OK, 1,2,4=Err)
display of
value EIS5
2 Byte
R
7.*
Summarized status feedback object to display service code in case
of service is required on pool. Telegram with code is sent to bus
cyclically every 600s. Code explanation:
1 - water quality long-term (OK/ERR)
2 - technology (OK/ERR)
4 - service intervals (OK/ERR)
10/1/2
LVLØ Circuit Breakers Status Feedback (0=OK, 1,2,4=Err)
display of
value EIS5
2 Byte
R
7.*
Summarized status feedback object to display exact service code in
case of Circuit breakers failure. Telegram with code is sent to bus
cyclically every 600s. Code explanation:
1 - dosing breaker failure (OK/ERR)
2 - filtration breaker failure (OK/ERR)
4 - additional technology breaker failure (OK/ERR)
10/1/3
LVLØ Water Treatment Status Feedback
display of
value EIS5
2 Byte
R
7.*
Summarized status feedback object to display exact service code in
case of water treatment issues. Telegram with code is sent to bus
cyclically every 600s. Code explanation:
1 - pH (OK/ERR)
2 - ORP/CLF (OK/ERR)
4 - chemical stocks (OK/ERR)
8 - electrodes (OK/ERR)
10/1/4
LVLØ Pump and Valves Status Feedback
display of
value EIS9
2 Byte
R
7.*
Display actual status of outputs for "DOSING PUMPS 1 - 4",
"FILTRATION", "3 WAY VALVE" and "MAKE UP WATER VALVE".
Summarized status telegram is sent to bus on change and cyclically
every 600s. Code explanation:
1 - filtration pump (ACTIVE/INACTIVE)
2 - dosing pump 1 (ACTIVE/INACTIVE)
4 - dosing pump 2 (ACTIVE/INACTIVE)
8 - dosing pump 3 (ACTIVE/INACTIVE)
16 - dosing pump 4 (ACTIVE/INACTIVE)
32 - heating valve (OPEN/CLOSE)
64 - make up water (OPEN/CLOSE)