Goodrive200 inverters Appendix C
256
C.6 Reactors
Transient high current in the input power circuit may cause damage to the rectifying
components. It is appropriate to use AC reactor in the input side for the avoidance of
high-voltage input of the power supply and improvement of the power factors.
If the distance between the inverter and the motor is longer than 50m, frequent overcurrent
protection may occur to the inverter because of high leakage current caused by parasitic
capacitance effects from the long cables to the ground. In order to avoid the damage of the
motor insulation, it is necessary to add reactor compensation. If the distance between the
inverter and motor is 50~100m, see the table below for model selection; if it exceeds 100m,
consult with INVT technical support.
All the inverters above 37kW (including 37kW) can add external DC reactors for the
improvement of power factors and the avoidance of damage from high input current to the
rectifying components because of the high-capacity transformer. The device can also cease
the damage to the rectifying components which are caused by supply net voltage transients
and harmonic waves of the loads.
The power of the inverter
Input reactor
DC reactor
Output reactor
GD200-1R5G-4
ACL2-1R5-4
/
OCL2-1R5-4
GD200-2R2G-4
ACL2-2R2-4
/
OCL2-2R2-4
GD200-004G/5R5P-4
ACL2-004-4
/
OCL2-004-4
GD200-5R5G/7R5P-4
ACL2-5R5-4
/
OCL2-5R5-4
GD200-7R5G/011P-4
ACL2-7R5-4
/
OCL2-7R5-4
GD200-011G/015P-4
ACL2-011-4
/
OCL2-011-4
GD200-015G/018P-4
ACL2-015-4
/
OCL2-015-4
GD200-018G/022P-4
ACL2-018-4
/
OCL2-018-4
GD200-022G/030P-4
ACL2-022-4
/
OCL2-022-4
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...