background image

2

3

1

2

3

1

Instruction Manual

PMH-24V50WCA

www.DeltaPSU.com

1.  Safety Instructions

•  To ensure sufficient convection cooling, always maintain a safety distance of ≥ 20mm 

from all ventilated surfaces while the device is in operation.

•  The device is not recommended to be placed on low thermal conductive surface, for 

example, plastics.

•  Note that the enclosure of the device can become very hot depending on the ambient 

temperature and load of the power supply. Do not touch the device while it is in operation 

or immediately after power is turned OFF. Risk of burning!

•  Do not touch the terminals while power is being supplied. Risk of electric shock.

•  Prevent  any  foreign  metal,  particles  or  conductors  to  enter  the  device  through  the 

openings during installation. It can cause: Electric shock; Safety Hazard; Fire; Product 

failure

•  The appliance is not to be used by persons (including children) with reduced physical, 

sensory or mental capabilities, or lack of experience and knowledge, unless they have 

been given supervision or instruction.

•  Warning:  When  connecting  the  device,  secure  Earth  connection  before  connecting  L 

and N. When disconnecting the device, remove L and N connections before removing 

the Earth connection.

•  The device is earthed and must be inaccessible.

2.  Device Descriptions

Refer to Fig. 1.:

 

Input & Output terminal block connector

 

DC voltage adjustment potentiometer (22V - 28V)

 

DC OK control LED (Green)

3.  Installation of the Device

Refer to Fig. 2.: 

 

Mounting holes for power supply assembly onto the mounting surface. The power supply 

shall be mounted on minimum 2 mounting holes using M3 screw minimum 5mm length.

 

This  surface  belongs  to  customer’s  end  system  or  panel  where  the  power  supply  is 

mounted.

 

Connector

•  Use flexible cable (stranded or solid) with the following sizes:

•  The torque at the Connector shall not exceed 13 Kgf.cm. The insulation stripping length 

should not exceed 0.275” or 7mm (Refer to Fig. 3).

4.  Installation of Mounting Accessories

Refer to Fig. 4.:

•  Only use M3 screw ≤ 6mm through the base mounting holes. This is to keep a safety 

distance between the screw and internal components.

•  Recommended mounting tightening torque: 4~8 Kgf.cm.

REV.00

Fig. 1. Device Descriptions

PMH-24V50WCAA (Standard Connector)

PMH-24V50WCAJ (IP20 Connector)

PMH-24V50WCAL (Front Face Connector)

Fig. 3. Wire Type

Fig. 4. Mounting Screw

Lug

Stripped wire

Mounting

accessories

Mounting

screw

Chassis of 

the device

6mm max.

7 mm

Fig. 2. Mounting Orientation

Side Mounting (Vertical)

Base Mounting (Vertical)

Side Mounting (Horizontal)

PMH-24V50WCAH (Harness Connector)

PMH-24V50WCAA

PMH-24V50WCAJ

PMH-24V50WCAL

AWG 20-14

AWG 20-12

AWG 20-12

A

C

B

B

B

C

A

C

A

A

C

B

B

B

C

A

C

A

A

C

B

B

B

C

A

C

A

3

1

Base surface

Top surface

Side surface

Ventilated surface

2

2

3

1

Содержание PMH-24V50WCA Series

Страница 1: ...s Refer to Fig 1 䐟 䐟 Input Output terminal block connector 䐠 䐠 DC voltage adjustment potentiometer 22V 28V 䐡 䐡 DC OK control LED Green 3 Installation of the Device Refer to Fig 2 䑵 䑵 Mounting holes for power supply assembly onto the mounting surface The power supply shall be mounted on minimum 2 mounting holes using M3 screw minimum 5mm length 䑶 䑶 This surface belongs to customer s end system or p...

Страница 2: ...確保螺絲和內部元件間有足夠的絕緣距離 建議配件固定螺絲扭矩為 4 8 Kgf cm 1 安全规范 与通风表面保持至少 20mm 的安全距离 以确保对流冷却充分 本产品不适合摆放在低热导体 例如 塑胶 受环境温度及产品负载的影响 本机外壳温度会很高 因此在上电时或切断电 源后短时间内不要触摸本机 以免烫伤 请勿在上电时触摸连接端子 以防电击危险 安装过程中 应避免金属元件或金属导体通过空隙或通风孔进入到产品内 否则会引起下列状况 电击 安全危害 火灾 产品异常 在肢体 感官或精神上有所限制的人士和没有受过适当训练或教育的人士 包括儿童 不能够在没有专人的协助和指导下使用该产品 警告 在连接产品电源供应时 产品必须先接地然后才接 L 和 N 当要解开电源 供应时 必须先把 L 和 N 解开然后才把接地解开 产品是接地的 并且不能被触碰 2 产品外观介绍 依据图一 䐟 䐟 输入 输出连接端子 䐠...

Отзывы: