Goodrive200 inverters Function codes
83
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
middle
setting of
AI3
The setting range of P05.45:-100.0%~100.0%
The setting range of P05.46:P05.44~10.00V
The setting range of P05.47:-100.0%~100.0%
The setting range of P05.48:0.000s~10.000s
P05.46
Upper limit
of AI3
10.00V
○
P05.47
Correspon
ding
setting of
the upper
limit of AI3
100.0%
○
P05.48
AI3 input
filter time
0.100s
○
P05.49
HDI
high-speed
pulse input
The function selection when HDI terminals is
high-speed pulse input
0:Frequency setting input, frequency setting
source
1:Counter input, high-speed pulse counter input
terminals
2:Length counting input, length counter input
terminals
0
◎
P05.50
Lower limit
frequency
of HDI
0.000kHz~P05.52
0.000
kHz
○
P05.51
Correspon
ding
setting of
HDI low
frequency
setting
-100.0%~100.0%
0.0%
○
P05.52
Upper limit
frequency
P05.50 ~50.00kHz
50.00
kHz
○
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...