Goodrive200 inverters Function codes
104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range of P08.29:0.1~3600.0s
P08.30
Frequency
decreasing
ratio of the
dropping
control
The output frequency of the inverter changes as
the load. And it is mainly used to balance the
power when several inverters drive one load.
Setting range:0.00~10.00Hz
0.00Hz
○
P08.31
Reserved
P08.32
FDT1
electrical
level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of “frequency level detect FDT”
until the output frequency decreases to a value
lower than (FDT electrical level—FDT retention
detection value) the corresponding frequency,
the signal is invalid. Below is the waveform
diagram:
Setting range of P08.32: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P08.33: -100.0~100.0%
(FDT1 electrical level)
50.00
Hz
○
P08.33
FDT1
retention
detection
value
5.0%
○
P08.34
FDT2
electrical
level
detection
value
50.00
Hz
○
P08.35
FDT2
retention
detection
value
5.0%
○
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...