![INVT GD200-037G/045P-4 Скачать руководство пользователя страница 228](http://html1.mh-extra.com/html/invt/gd200-037g-045p-4/gd200-037g-045p-4_operation-manual_2085736228.webp)
Goodrive200
inverters Communication protocol
227
the loop detection to address 01H of driver is carried out.
The RTU request command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
08H
High bit of sub-function code
00H
Low bit of sub-function code
00H
High bit of data content
12H
Low bit of data content
ABH
Low bit of CRC
ADH
High bit of CRC
14H
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
The RTU response command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
08H
High bit of sub-function code
00H
Low bit of sub-function code
00H
High bit of data content
12H
Low bit of data content
ABH
Low bit of CRC
ADH
High bit of CRC
14H
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
10.4.4 Command code: 10H, continuous writing
Command code 10H means that if the master writes data to the inverter, the data number
depends on the “data number” in the command code. The Max. continuous reading number
is 16.
For example, write 5000(1388H) to 0004H of the inverter whose slave address is 02H and
50(0032H) to 0005H, the frame structure is as below:
The RTU request command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
02H
CMD
10H
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...