Goodrive200
inverters Basic operation instruction
171
Set
value
Function
Instructions
22
ACC/DEC time selection 2
terminals.
Terminal
1
Terminal
2
ACC/DEC time
selection
Corresponding
parameter
OFF
OFF
ACC/DEC time 1 P00.11/P00.12
ON
OFF
ACC/DEC time 2 P08.00/P08.01
OFF
ON
ACC/DEC time 3 P08.02/P08.03
ON
ON
ACC/DEC time 4 P08.04/P08.05
23
Simple PLC stop reset
Restart simple PLC and clear the memory state of
PLC.
24
Simple PLC pause
Program pause during PLC implement. Run at the
current speed step. After cancel the function, simple
PLC continues to run.
25
PID control pause
Temporal PID invalid and the inverter will output at the
current frequency.
26
Traverse pause (stop at the
current frequency)
The inverter will stop at the current output and after
canceling the function, the inverter will continue to
traverse run at the current frequency.
27
Traverse reset (return to the
middle frequency)
The setting frequency of the inverter will come back to
the middle frequency.
28
Counter reset
Counter clear
29
Torque control prohibition
Switch from torque control mode to speed control
mode
30
ACC/DEC disabling
Ensure the inverter will not be affected by the external
signals (except for the stopping command) and keep
the current output frequency.
31
Counter trigging
Enable the pulse counter.
32
Length reset
Length counter clear
33
Frequency
increasing/decreasing setting
temporal clear
When the terminal closes, the frequency set by
UP/DOWN can be cleared. All set frequency will be
restored into the reference frequency by the
frequency command channel and the frequency will
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...