Goodrive200 inverters Function codes
117
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
speed 6 16 steps speed via the combination code of S1,
S2, S3, and S4.
The start-up and stopping of multi-step running is
determined by function code P00.06, the
relationship between S1,S2,S3,S4 terminals and
multi-step speed is as following:
S1 OFF ON OFF ON OFF ON OFF ON
S2 OFF OFF ON ON OFF OFF ON ON
S3 OFF OFF OFF OFF ON ON ON ON
S4 OFF OFF OFF OFF OFF OFF OFF OFF
Step 0
1
2
3
4
5
6
7
S1 OFF ON OFF ON OFF ON OFF ON
S2 OFF OFF ON ON OFF OFF ON ON
S3 OFF OFF OFF OFF ON ON ON ON
S4 ON ON ON ON ON ON ON ON
Step 8
9
10
11
12
13
14
15
Setting range of P10.(2n,1<n<17):
-100.0~100.0%
Setting range of
P10.(2n+1,1<n<17):0.0~6553.5s(min)
P10.15
The
running
time of
step 6
0.0s
○
P10.16
Multi-step
speed 7
0.0%
○
P10.17
The
running
time of
step 7
0.0s
○
P10.18
Multi-step
speed 8
0.0%
○
P10.19
The
running
time of
step 8
0.0s
○
P10.20
Multi-step
speed 9
0.0%
○
P10.21
The
running
time of
step 9
0.0s
○
P10.22
Multi-step
speed 10
0.0%
○
P10.23
The
running
time of
step 10
0.0s
○
P10.24
Multi-step
speed 11
0.0%
○
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...