Goodrive200
inverters Basic operation instruction
153
Relative parameters list:
Function
code
Name
Detailed instruction of parameters
Default
value
P00.01
Run command channel
0:Keypad running command
channel(LED off)
1:Terminal running command channel
(LED flickering)
2:Communication running command
channel (LED on)
0
P00.11
ACC time 1
0.0~3600.0s
Depend
on model
P00.12
DEC time 1
0.0~3600.0s
Depend
on model
P01.00
Start mode
0:Start-up directly
1:Start-up after DC braking
2: Start-up after speed tracking
0
P01.01
Starting frequency of
direct start
0.00~50.00Hz
0.50Hz
P01.02
Retention time of the
starting frequency
0.00~50.00s
0.00s