Goodrive200 inverters Fault tracking
205
Fault code
Fault type
Possible cause
What to do
STo
Maladjustment
fault
The control parameters of
the synchronous motors
not set properly
The autoturn parameter is
not right
The inverter is not
connected to the motor
Check the load and
ensure it is normal
Check whether the control
parameter is set properly
or not
Increase the
maladjustment detection
time
END
Time reach of
factory setting
The actual running time of
the inverter is above the
internal setting running
time
Ask for the supplier and
adjust the setting running
time
PCE
Keypad
communication
fault
The connection of the
keypad wires is not good
or broken
The keypad wire is too
long and affected by
strong interference
There is circuit fault on the
communication of the
keypad and main board
Check the keypad wires
and ensure whether there
is mistake
Check the environment
and avoid the interference
source
Change the hardware and
ask for service
DNE
Parameters
downloading fault
The connection of the
keypad wires is not good
or broken
The keypad wire is too
long and affected by
strong interference
There is mistake on the
data storage of the keypad
Check the keypad wires
and ensure whether there
is mistake
Change the hardware and
ask for service
Repack-up the data in the
keypad
LL
Electronic
underload fault
The inverter will report the
underload pre-alarm
according to the set value
Check the load and the
underload pre-alarm point
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...