![INVT GD200-037G/045P-4 Скачать руководство пользователя страница 203](http://html1.mh-extra.com/html/invt/gd200-037g-045p-4/gd200-037g-045p-4_operation-manual_2085736203.webp)
Goodrive200 inverters Fault tracking
202
Fault code
Fault type
Possible cause
What to do
OL1
Motor overload
The voltage of the power
supply is too low
The motor setting rated
current is incorrect
The motor stall or load
transients is too strong
Check the power of the
supply line
Reset the rated current of
the motor
Check the load and adjust
the torque lift
OL2
Inverter overload
The acceleration is too
fast
Reset the rotating motor
The voltage of the power
supply is too low
The load is too heavy
The motor power is too
small
Increase the ACC time
Avoid the restarting after
stopping
Check the power of the
supply line
Select an inverter with
bigger power
Select a proper motor
OL3
Electrical overload
The inverter will report
overload pre-alarm
according to the set value
Check the load and the
overload pre-alarm point.
SPI
Input phase loss
Phase loss or fluctuation
of input R,S,T
Check input power
Check installation
distribution
SPO
Output phase loss
U,V,W phase loss input(or
serious asymmetrical
three phase of the load)
Check the output
distribution
Check the motor and
cable
OH1
Rectify overheat
Air duct jam or fan
damage
Ambient temperature is
too high
The time of overload
running is too long
Clean the air duct or the
fan
Reduce the ambient
temperature
OH2
IGBT overheat
EF
External fault
SI external fault input
terminals action
Check the external device
input
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...