Goodrive200
inverters Basic operation instruction
155
Function
code
Name
Detailed instruction of parameters
Default
value
P01.23
Start delay time
0.0~60.0s
0.0s
P01.24
Delay time of the stop
speed
0.0~10.0 s
0.0s
P05.01~P0
5.09
Digital input function
selection
1: Forward rotation operation
2: Reverse rotation operation
4: Forward rotation jogging
5: Reverse rotation jogging
6: Coast to stop
7: Fault reset
8: Operation pause
21:ACC/DEC time option1
22:ACC/DEC time option2
30:ACC/DEC prohibition
P08.06
Jogging frequency
0.00~P00.03(the Max. frequency)
5.00Hz
P08.07
Jogging ACC time
0.0~3600.0s
Depend
on model
P08.08
Jogging DEC time
0.0~3600.0s
Depend
on model
P08.00
ACC time 2
0.0~3600.0s
Depend
on model
P08.01
DEC time 2
0.0~3600.0s
Depend
on model
P08.02
ACC time 3
0.0~3600.0s
Depend
on model
P08.03
DEC time 3
0.0~3600.0s
Depend
on model
P08.04
ACC time 4
0.0~3600.0s
Depend
on model
P08.05
DEC time 4
0.0~3600.0s
Depend
on model
P08.28
Fault reset times
0~10
0
Содержание GD200-037G/045P-4
Страница 1: ...Goodrive 200 Inverter ...
Страница 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Страница 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Страница 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Страница 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Страница 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Страница 245: ...Goodrive200 inverters Appendix B 244 B 3 Inverter chart B 4 Inverter chart B 4 1 Wall mounting 1 5 30kW wall mounting ...
Страница 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...