Goodrive20-EU series VFD
Peripheral options and parts
153
Model
Recommended
cable size (mm
2
)
Connecting cable size
(mm
2
)
Terminal
screw
Tightening
torque (Nm)
RST
PE
RST
P1, (+)
PE
UVW
UVW
GD20-055G-4-EU
50
25
35
– 70 35 – 70 16 – 35
M8
10
GD20-075G-4-EU
70
35
35
– 70 35 – 70 16 – 35
M8
10
GD20-090G-4-EU
95
50
70
– 120 70 – 120 50 – 70
M12
35
GD20-110G-4-EU 120
70
70
– 120 70 – 120 50 – 70
M12
35
Note:
1.
It is appropriate to use the recommended cable size under 40°C and rated current. The
wiring distance should be no more than 100m.
2.
Terminals P1, (+), PB and (-) connects the DC reactor options and parts.
C.4 Breaker and electromagnetic contactor
It is necessary to add fuse for the avoidance of overload.
It is appropriate to use a breaker (MCCB) which complies with the VFD power in the 3-phase
AC power and input power and terminals. The capacity of the VFD should be 1.5-2 times of
the rated current.
Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases may
escape from the breaker enclosure in case of a short-circuit. To ensure
safe use, special attention must be paid to the installation and
placement of the breakers. Follow the manufacturer's instructions.
It is necessary to install the electromagnetic contactor in the input side to control the switching
on and off safety of the main circuit. It can switch off the input power supply when system
faults.
Model
Fuse (A)
Breaker
(A)
Rated working current
of the contactor (A)
GD20-0R4G-S2-EU
10
10
9
GD20-0R7G-S2-EU
16
16
12
GD20-1R5G-S2-EU
25
25
25
GD20-2R2G-S2-EU
50
40
32
GD20-0R4G-2-EU
6
6
9
GD20-0R7G-2-EU
10
10
9
GD20-1R5G-2-EU
16
16
12
GD20-2R2G-2-EU
25
25
18
GD20-004G-2-EU
35
32
25