Goodrive20-EU series VFD
Function parameters
76
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The raising time of the traverse frequency: The
time from the lowest point to the highest one.
The declining time of the traverse frequency: The
time from the highest point to the lowest one.
Setting range of P08.15: 0.0
– 100.0%
(relative to the set frequency)
Setting range of P08.16: 0.0
– 50.0%
(relative to the traverse range)
Setting range of P08.17: 0.1
– 3600.0s
Setting range of P08.18: 0.1
– 3600.0s
P08.19
Linear speed/
frequency
decimals
Ones: decimals of linear speed display
0: no decimals
1: one decimal
2.: two decimals
3: three decimals
Tens: decimals of frequency display
0: two decimals
1: one decimal
0x00
○
P08.20
Analog
calibration
function setting
0: Disabled
1: Enabled
0
◎
P08.21
Deceleration
time for
emergency
stop
0.0
–6553.5s
0.0 indicates coasting to stop.
0.0s
○
P08.22
Delay to enter
the sleep state
0.0
–3600.0s
It indicates the delay to enter the sleep state, and
it is valid only when P01.19 is set to 2.
2.0s
○
P08.23
Preset voltage
and frequency
0: 230 V preset voltage and 50Hz preset frequency
1: 220 V preset voltage and 60Hz preset frequency
2: 400 V preset voltage and 50Hz preset frequency
3: 460 V preset voltage and 60Hz preset frequency
2
◎
P08.24
Enabling
energy
consumption
braking stop
0: Disable
1: Enable
1
○