Goodrive20-EU series VFD
Function parameters
82
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
0: Save when power off
1: Clear when power off
LED tens: Action of the set MODBUS frequency
at power off
0: Save when power off
1: Clear when power off
LED hundreds: Action of the other
communication frequencies at power off
0: Save when power off
1: Clear when power off
P08.48
High bit of
original power
consumption
value
This parameter is used to set the original value of
the power consumption.
The original value of the power consumption
Setting range of P08.48: 0
– 59999
Setting range of P08.49: 0.0
– 999.9
0
○
P08.49
Low bit of
original power
consumption
value
0.0
○
P08.50
Flux brake
coefficient
This function code is used to enable magnetic
flux.
0: Invalid.
100
– 150: the bigger the coefficient, the bigger
the braking strength.
This VFD can slow down the motor by increasing
the magnetic flux. The energy generated by the
motor during braking can be transformed into
heat energy by increasing the magnetic flux.
The VFD monitors the state of the motor
continuously even during magnetic flux period.
So the magnetic flux can be used in the motor
stop, as well as to change the rotation speed of
the motor. Its other advantages are:
Brake immediately after the stop command. It
does not need to wait the magnetic flux weaken.
The cooling is better. The current of the stator
other than the rotor increases during magnetic
flux braking, while the cooling of the stator is
more effective than the rotor.
0
○