Goodrive20-EU series VFD
Function parameters
39
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00.18
Function
restore
parameter
0: No operation
1: Restore the default value
2: Clear fault records
3: Lock all function codes
Note:
The function code will restore to 0 after
finishing the operation of the selected function
code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0
◎
P01 Group Start-up and stop control
P01.00
Start mode
0: Start-up directly: start from the starting
frequency P01.01
1: Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
2: Start after speed tracking 1
3: Start after speed tracking 2
The direction and speed will be tracked
automatically for the smoothing starting of
rotating motors. It suits the application with
reverse rotation when big load starting.
Note:
This function is only available for the
VFDs≥4kW
0
◎
P01.01
Starting
frequency of
direct start-up
Starting frequency of direct start-up means the
original frequency during the VFD starting. See
P01.02 for detailed information.
Setting range: 0.00
– 50.00Hz
0.50Hz
◎
P01.02
Hold time of
the starting
frequency
Set a proper starting frequency to increase the
torque of the VFD during starting. During the
retention time of the starting frequency, the
output frequency of the VFD is the starting
frequency. And then, the VFD will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the VFD will stop running and keep in the
0.0s
◎