Goodrive20-EU series VFD
Function parameters
95
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P11.16
Extension
function
selection
0x000
– 0x111
LED ones: Automatic frequency-drop at voltage
drop
0: Automatic frequency-drop at voltage drop is
invalid
1: Automatic frequency-drop at voltage drop is
valid
LED tens: The second acceleration/deceleration
time selection
0: The second acceleration/deceleration time
detection selection is invalid
1: The second acceleration/deceleration time
detection selection is valid;
when the operation is above P08.36,
acceleration/deceleration time is switched to the
second acceleration/deceleration time
LED hundreds: STO function selection
0: STO alarm locked
Alarm locked means when STO appears, reset is
a must after state recovery.
1: STO alarm unlocked
STO alarm unlocked means when STO appears,
STO alarm will disappeared automatically after
state recovery.
Note: STL1
– STL3 are fault lock and cannot be
reset
0x000
○
P13 Group Control parameters of SM
P13.13
Short circuit
brake current
After the VFD starts, when P01.00=0, set P13.14
to non-zero value and begin short circuit braking.
After the VFD stops, when the operation
frequency is less than P01.09, set P13.15 to
non-zero value and begin stopping short-circuit
braking and then DC braking.
Setting range of P13.13: 0.0
– 150.0% (VFDs)
Setting range of P13.14: 0.00
– 50.00s
0.0%
○
P13.14
Hold time of
short circuit
brake at start
0.00s
○
P13.15
Hold time of
short circuit
brake at stop
0.00s
○