Goodrive20-EU series VFD
Function parameters
33
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
2: SVPWM control
Suitable in applications which do not need high
control accuracy, such as the load of fan and
pump. One VFD can drive multiple motors.
Note: Motor parameter autotuning is required
when vector mode is applied.
P00.01
Run command
channel
Select the run command channel of the VFD.
The control command of the VFD includes: start,
stop, forward/reverse rotating, jogging and fault
reset.
0: Keypad ("LOCAL/REMOT" light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG to
FWD/REVC shifting function (P07.02=3) to
change the running direction; press
RUN
and
STOP/RST
simultaneously in running state to
make the VFD coast to stop.
1: Terminal ("LOCAL/REMOT" flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2:Communication ("LOCAL/REMOT" on);
The running command is controlled by the upper
monitor via communication
0
○
P00.03
Max. output
frequency
This parameter is used to set the maximum
output frequency of the VFD. Users need to pay
attention to this parameter because it is the
foundation of the frequency setting and the
speed of acceleration and deceleration.
Setting range: P00.04
– 400.00Hz
50.00Hz
◎
P00.04
Upper limit of
running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the VFD
which is lower than or equal to the maximum
frequency.
Setting range: P00.05
frequency)
50.00Hz
◎