Goodrive20-EU series VFD
Technical data
141
Derating coefficient (%)
Altitude (m)
100
80
60
40
20
0
1000
2000
3000
4000
When the altitude exceeds 2000m, configure an isolation transformer on the input end of the
VFD.
When the altitude exceeds 3000m but is lower than 5000m, contact our company for technical
consultation. Do not use the VFD at an altitude higher than 5000m.
A.2 CE
A.2.1 CE marking
The CE mark is attached to the drive to verify that the drive follows the provisions of the
European Low Voltage (2006/95/EC) and EMC Directives (2004/108/EC).
A.2.2 Compliance with the European EMC Directive
The EMC Directive defines the requirements for immunity and emissions of electrical
equipment used within the European Union. The EMC product standard (EN 61800-3:2004)
covers requirements stated for drives. See section
EMC regulations
A.3 EMC regulations
EMC product standard (EN 61800-3:2004) contains the EMC requirements to the VFD.
First environment: domestic environment (includes establishments connected to a low-voltage
network which supplies buildings used for domestic purposes).
Second environment includes establishments connected to a network not directly supplying
domestic premises.
Four categories of the VFD:
VFD of category C1: VFD of rated voltage less than 1000 V and used in the first environment.
VFD of category C2: VFD of rated voltage less than 1000 V other than pins, sockets and
motion devices and intended to be installed and commissioned only by a professional
electrician when used in the first environment.
Note:
IEC/EN 61800-3 in EMC standard doesn't limit the power distribution of the VFD, but it
defines the upstage, installation and commission. The professional electrician has necessary
skills in installing and/or commissioning power drive systems, including their EMC aspects.
VFD of category C3: VFD of rated voltage less than 1000 V and used in the second