Goodrive20-EU series VFD
Product overview
8
Function
Specification
Contact capacity: 3A/AC250V
*Relay 2 output only available on GD20-EU > 2.2kW
Others
DC reactor
Standard embedded DC reactor for the VFDs
(≥18.5kW)
Installation mode
Wall and rail installation of the VFDs (single phase
230V/three phase 400V, ≤2.2KW and three phase
230V, ≤0.75KW)
Wall and flange installation of the VFDs (three
phase 400V, ≥4KW and three phase 230V, ≥1.5KW)
Brake unit
Standard for the VFDs
≤37kW and optional for the
VFDs within 45
– 110kW
EMI filter
3PH 400V 4kW and above/3PH 230V 1.5kW and
above can comply with IEC61800-3 class C3,
others can meet requirements of IEC61800-3 class
C3 by installing external filter (optional). This series
of products can comply with IEC61800-3 class C2
by installing external filter (optional).
Ambient temperature
-10 to 50°C, derate 1% for every increased 1°C
when the temperature is higher than 40°C
Altitude
Below 1000m. If the elevation is above 1000m,
derate 1% for every additional 100m.
Ingress protection (IP)
rating
IP20
Note: The VFD with plastic casing should be
installed in metal distribution cabinet which
conforms to IP20 and the top of which conforms to
IP3X.
Pollution level
Level 2
Safety regulation
Comply with CE requirements
Cooling
Air cooling
Содержание GD20-004G-2-EU