Goodrive20-EU series VFD
Installation guide
15
Environment
Conditions
Storage
temperature
-40°C to +70°C, and the temperature changing rate is less than 1°C/minute.
Running
environment
condition
The installation site of the VFD should fulfill the following requirements.
a) Away from the electromagnetic radiation source;
b) Away from contaminative air, such as corrosive gas, oil mist and
flammable gas;
c) Foreign objects, such as metal power, dust, oil, water cannot fall into the
VFD (do not install the VFD on the flammable materials such as wood);
d) Away from direct sunlight, oil mist, steam and vibration environment.
Altitude
Below 1000m;
If the altitude is above 1000m, derate 1% for every additional 100m.
Vibration
≤ 5.8m/s
2
(0.6g)
Installation
direction
The VFD should be installed on an upright position to ensure sufficient cooling
effect.
Note:
Goodrive20-EU series VFDs should be installed in a clean and ventilated environment
according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
3.1.2 Installation direction
The VFD may be installed on the wall or in a cabinet.
The VFD needs be installed in the vertical position. Check the installation site according to the
requirements below. Refer to Appendix B "Dimension drawings" for details.
3.1.3 Installation mode
(1) Wall and rail mounting for the VFDs (single phase 230V/three phase
400V, ≤2.2KW and
three phase 230V, ≤0.75KW)
a) Wall mounting
b) Rail mounting
Figure 3-1 Installation