Goodrive20-EU series VFD
Installation guide
20
S1
S2
S3
S4
HDI
Y1
AI2
AI3
+24V
PW
COM
COM
GND
AO1
AO2
485+
RO1A
RO1B
RO1C
RO2A
RO2B
RO2C
+10V
485-
+24V
H1
+24V
H2
Figure 3-11
Connection terminal diagram for VFDs ≥ 4kW
Type
Terminal
name
Function
description
Technical specifications
Communication
485+
485 communication
485 communication interface
485-
Digital
input/output
S1
Digital input
1. Internal impedance:
3.3kΩ
2. 12
– 30V voltage input is available
3. The terminal is the dual-direction input
terminal
4. Max. input frequency: 1kHz
S2
S3
S4
HDI
High frequency
input channel
Except for S1
– S4, this terminal can be
used as high frequency input channel.
Max. input frequency: 50kHz
Duty cycle: 30%
– 70%
PW
Digital power supply
The working power of digital input is
provided by an external power supply.
Power range: 12 V
–30 V
Y1
Digital output
1. Contact capacity: 50mA/30V;
2. Output frequency range: 0
– 1kHz;
3. Default is STO state output indicator.
STO function
input
24V-H1
STO input 1
1. Safe torque stop (STO) redundant input,
externally connected to NC contact, STO
acts when the contact is open, and the
drive stops output;
2. The safe input signal cable should be
shield cable within 25m.
3. When employing STO function, please
disassemble the short circuit plate on the
terminals shown in fig 3.10 and fig 3.11.
24V-H2
STO input 2
24V power
supply
+24V
24V power supply
External 24V±10% power supply and the
maximum output current is 200mA
。
Generally used as the operation power
supply of digital input and output or external
sensor power supply
COM