Appendix A Parameter Table
- 76 -
Param.
No.
Param. Name
Setting Range
Default
Property
F8-33 Detection width of
frequency 2
0.0% to 100.0% (maximum frequency)
0.0%
☆
F8-34 Zero current detec-
tion level
0.0% to 300.0%
The value 100.0% corresponds to the rated
motor current.
5.0%
☆
F8-35 Zero current detec-
tion delay
0.01s to 600.00s
0.10s
☆
F8-36 Output overcurrent
threshold
0.0% (no detection)
0.1% to 300.0% (rated motor current)
200.0%
☆
F8-37 Output overcurrent
detection delay
0.00s to 600.00s
0.00s
☆
F8-38 Detection level of
current 1
0.0% to 300.0% (rated motor current)
100.0%
☆
F8-39 Detection width of
current 1
0.0% to 300.0% (rated motor current)
0.0%
☆
F8-40 Detection level of
current 2
0.0% to 300.0% (rated motor current)
100.0%
☆
F8-41 Detection width of
current 2
0.0% to 300.0% (rated motor current)
0.0%
☆
F8-42 Timing function
0: Disabled
1: Enabled
0:
★
F8-43 Timing duration
source
0: Set by F8-44
1: AI1
2: AI2
AI range dependent on F8-44
0
★
F8-44 Timing duration
0.0 min to 6500.0 min
0.0 min
★
F8-45 AI1 input voltage
lower limit
0.00 V to F8-46 (AI1 input voltage upper
limit)
3.10 V
☆
F8-46 AI1 input voltage
upper limit
F8-45 (AI1 input voltage lower limit) to
11.00 V
6.80 V
☆
F8-47 IGBT temperature
threshold
0℃ to 100℃
75℃
☆
F8-48 Cooling fan working
mode
0: Working during drive running
1: Working continuously
0
☆
F8-49 Wakeup frequency
F8-51 (Hibernating frequency) to F0-10
(Maximum frequency)
0.00 Hz
☆
F8-50 Wakeup delay
0.0s to 6500.0s
0.0s
☆
F8-51 Hibernating frequen-
cy
0.00 Hz to F8-49 (Wakeup frequency)
0.00 Hz
☆
F8-52 Hibernating delay
0.0s to 6500.0s
0.0s
☆
F8-53 Current running time
reached
0.0 min to 6500.0 min
0.0 min
☆
F8-54 STO function
0: Disabled
1: Enabled
0
☆
F8-55 Deceleration time for
emergency stop
0.0s to 6500.0s
0.0
☆
F8-56 Jog by LED panel
0
0:
☆