Appendix A Parameter Table
- 73 -
Param.
No.
Param. Name
Setting Range
Default
Property
F6-20
Voltage rise time at
catching a spinning
motor
0.5s to 3.0s
1.0s
☆
F6-21 Demagnetization
time
00.00s to 10.00s
1.00s
☆
F6-22 Startup pre-torque
setting
000.0% to 200.0%
0.0%
☆
F6-23
Operation at com-
mand from power
supply unit
0: Stop according to F6-10
1: Ignore stop command
0
★
F6-24 Position lock KP
0.0 to 100.0
10.0
☆
F6-25 Position lock end
amplitude
0 to 16383
10
☆
Group F7: Keypad Operation and LED Display
F7-03 LED display running
parameter 1
0000 to FFFF
Bit00: Running frequency (Hz)
Bit01: Frequency reference (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI state
Bit08: DO state
Bit09: AI1 voltage
Bit10: AI2 voltage (V)
Bit11: Reserved
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID reference
1F
☆
F7-04 LED display running
parameter 2
0000 to FFFF
Bit00: PID feedback
Bit01: PLC stage
Bit02: Pulse input frequency (kHz)
Bit03: Running frequency 2 (Hz)
Bit04: Remaining running time
Bit05: AI1 voltage before correction (V)
Bit06: AI2 voltage before correction (V)
Bit07: Reserved
Bit08: Linear speed
Bit09: Current power-on time (h)
Bit10: Current running time (min)
Bit11: Pulse input frequency (Hz)
Bit12: Communication setting value
Bit13: Reserved
Bit14: Main frequency X display (Hz)
Bit15: Auxiliary frequency Y display (Hz)
0
☆