4 Troubleshooting
- 49 -
Fault
Code
Fault Description
Possible Cause
Solution
Err94
Stop after tem-
perature pre-warn-
ing time exceeded
Duration from the tempera-
ture pre-warning reported ≥
Long-time stop pre-warning
time
See the solutions for Err72/A73.
Err95
Solenoid valve
overcurrent
1)
The model and specifi
-
cations of the solenoid
valve are not suitable for
the transformer.
2) The solenoid valve is
broken.
3) When the AC drive is run-
ning with load, the TA/
TC terminal has no 220 V
output.
1) Check whether the model and
specifications of the solenoid
valve are suitable for the trans-
former (AC 110/220 V).
2) Replace the solenoid valve.
3) Contact the agent or Inovance for
technical support.
Err96
Phase sequence
abnormal
Three-phase input sequence
abnormal (R, S, T)
Exchange any two of the phase se-
quences.
Err97
Output phase loss
of mains frequency
cooling blower
1) The motor wiring is incor-
rect.
2) The motor cooling blower
is damaged.
3) The fuse is loose or dam-
aged.
1) Wire the motor properly.
2) Use a multimeter to measure
the resistance between phases.
If open circuit exists, replace the
motor cooling blower.
3) Fix the fuse properly or replace the
fuse.
Err98
Low pump pres-
sure
1) The water pump function
is not provided, and the
DI terminal is allocated
with function 59.
2) The water pump function
is provided, and the DI
terminal is allocated with
function 59.
1) Allocate the DI terminal with func-
tion 0.
2) If the water pump is abnormal,
repair or replace it.
Err99
Mains frequency
cooling blower
overload
1) The mains frequency
cooling blower is with
high specifications.
2) The motor cooling blower
is blocked or stuck with a
foreign matter.
1) Select a suitable cooling blower.
2) Clear the foreign matter.