Appendix A Parameter Table
- 71 -
Param.
No.
Param. Name
Setting Range
Default
Property
F5-06 FMP output function
selection
0: Output frequency
1: Set frequency
2: Output current
3: Output torque (100.0% corresponding to
two times of the rated motor torque)
4: Output power
5: Output voltage (100% corresponding to
1.2 times of the rated AC drive voltage)
6: Pulse reference (100% corresponding to
50.0 kHz)
7: AI1
8: AI2
9: Reserved
10: Length
11: Count value
12: Communication setting
13: Motor speed
14: Output current (100.0% corresponding
to 1000.0 A)
15: Output voltage (100.0% corresponding
to 1000.0 V)
16: Output torque (directional,100.0%
corresponding to two times of the rated
motor torque)
19: Taper output
0
☆
F5-07 AO1 function selec-
tion
0
☆
F5-09 Maximum FMP output
frequency
0.01 kHz to 100.00 kHz
50.00 kHz
☆
F5-10
AO1 zero offset coeffi
-
cient
-100.0% to +100.0%
0.0%
☆
F5-11 AO1 gain
-10.00 to +10.00
1.00
☆
F5-17 FMR output delay
0.0s to 3600.0s
0.0s
☆
F5-18 Relay 1 output delay 0s to 65535s
0s
☆
F5-19 Relay 2 output delay 0s to 65535s
0s
☆
F5-20 DIO1 output delay
0.0s to 3600.0s
0.0s
☆
F5-22 DO active mode
selection
0: Positive logic active
1: Negative logic active
Ones: FMR (DIO2)
Tens: RELAY1
Hundreds: Reserved
Thousands: DIO1
Ten thousands: Reserved
0
☆
F5-23 AO1 mode selection 0: Voltage output
1: Current output
0
★