APRIL 2020 • REVISION 4.0
INSTRUCTION MANUAL
47
Upon completion of a ProXcide™ process a portable gas monitor should be used to check that
the treatment area is safe to enter.
It may also be used in the event of process failure, such as due to power failure, to assess when it
is safe to re-enter the room and investigate the cause of the failure.
Requirements
1.
ATI Porta Sens II portable gas leak detector model C 16 or equivalent gas detector.
2.
Hydrogen peroxide sensor with 0 to 20ppm calibration range.
Instructions
1.
Set up the gas leak detector and probe according to the user manual.
2.
Check that the sensor calibration is in date.
3.
Switch on the gas leak detector (normally set in continuous reading mode). The screen
should read 0 ppm.
4.
Position the gas leak detector probe tip only into the treatment space either through any
gap (e.g. door seal) or by slightly opening the door. The main body of the gas leak detector
and the Operator should remain outside of the treatment space.
5.
Wait until the gas leak detector has stabilised and note the reading.
6.
If reading is > 2.0ppm then remove the probe and close the door if it is open. Wait 15
minutes before attempting to re-measure the hydrogen peroxide vapour levels. If reading
is 1 - 2 ppm then you may enter the room for a maximum of 15 mins / 8 hr period to open
windows and increase ventilation, before closing the door again and waiting another 15
minutes.
7.
Repeat from step 3 until a safe level of <1ppm is reached.
Note:
In the event of sustained or unusual trends in hydrogen peroxide vapour residue at the end of
the process, contact the Inivos through the relevent helpline displayed at the bottom of every other
page.
5.7
Using a portable gas leak detector
Содержание ProXcide
Страница 8: ...8 www inivos com INSTRUCTION MANUAL REVISION 4 0 APRIL 2020 1 2 ...
Страница 41: ...APRIL 2020 REVISION 4 0 INSTRUCTION MANUAL 41 Issue 4 Pop up box for issue 4 ...
Страница 42: ...42 www inivos com INSTRUCTION MANUAL REVISION 4 0 APRIL 2020 Issue 5 Pop up box for issue 5 ...
Страница 43: ...APRIL 2020 REVISION 4 0 INSTRUCTION MANUAL 43 Issues 12 Pop up box for issue 12 ...
Страница 44: ...44 www inivos com INSTRUCTION MANUAL REVISION 4 0 APRIL 2020 Issue 13 Pop up box for issue 13 ...
Страница 45: ...APRIL 2020 REVISION 4 0 INSTRUCTION MANUAL 45 Issues 16 to 20 Pop up box for issues 16 20 ...