Pin 7 is the common negative pole for all inputs and is connected to the negative pole
of the voltage source. The allocation of functions for pins 1 to 6 can be changed,
5.6 Connecting the PLC inputs to the electrical
system
WARNING
Danger due to components subjected to electrical overload
Material damage or personal injury can result from current that is too high at the inputs
and outputs.
► The voltage at the I/O port with regard to the protective conductor cable or the
ground potential must be less than 48 V DC or 25 V AC.
Technical data for the
PLC outputs
Nominal output voltage
±24 V DC
Maximum output voltage
28 V DC
Maximum sum of the currents for the
output pins 8…11
0.75 A (protection via an internal fuse)
Maximum sum of the currents for the
output pins 12…15
0.75 A (protection via an internal fuse)
Fig. 14: Electrical connection for the PLC inputs and outputs