900861-00D
7
IHP.us.com
FRAMING FIREPLACE
Disclaimer: BTU listings are based on 7.0” WC for Natural Gas
at the inlet side of gas valve. Flex line size and proper gas pipe
sizing will also affect BTU’s. As a result your BTU’s may vary
slightly from Table 1 specifications.
The fireplace ships on a wooden skid. Remove the screws as
shown in Figure 4 and lift fireplace off of skid.
NOTE: These fireplaces come shipped as Natural Gas models only. There is a conversion kit available as an accessory. Ensure you order
the specific conversion kit for your model fireplace. Table 1 shows the applicable information if converting to Liquid Propane (LP) gas.
IMPORTANT: The pilot hood must be on the windsheild side of the appliance to provide oxygen to the pilot during operation.
Figure 4 - Remove Fireplace from Skid
SPECIFICATIONS
Inlet Gas Pressure
Natural Gas (NG)
Propane (LP)
Minimum Inlet
5.0” WC (1.24 kPa)
10.5” WC (2.61 kPa)
Maximum Inlet 10.5” WC (2.61 kPa) 13.0” WC (3.23 kPa)
Normal Inlet
7.0” WC (1.74 kPa)
11.0” WC (2.74 kPa)
Manifold Gas Pressure
Natural Gas (NG)
Propane (LP)
Normal Mani-
fold
4” WC (1.00 kPa)
10.0” WC (2.49 kPa)
Table 2 - Gas Pressures
Model:
NG Factory
Orifice
NG BTU’s
High
NG BTU’s
Low
NG Low
Rate Screw
LP Factory
Orifice
LP BTU’s
High
LP BTU’s
Low
LP Low
Rate Screw
ODLVF36ZEN
#41
31,000
(9.08 kWh)
18,500
(5.42 kWh)
#44
#52
30,000
(8.79 kWh)
19,500
(5.72 kWh)
#52
ODLVF48ZEN
#32
43,500
(12.75 kWh)
24,500
(7.18 kWh)
#34
#48
42,500
(12.46 kWh)
29,000
(8.50 kWh)
#46
ODLVF60ZEN
#30
50,000
(14.65 kWh)
36,000
(10.55 kWh)
#27
#44
50,000
(14.65 kWh)
36,000
(10.55 kWh)
#42
ODLVF72ZEN
#25
65,000
(19.05 kWh)
42,000
(12.31 kWh)
#18
#42
60,000
(17.58 kWh)
45,000
(13.19 kWh)
#35
Table 1 - Fireplace Input Specifications
NOTE: Number of screws
vary with model size.