13: T
ROUBLESHOOTING
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
13-15
Troubleshooting Diagram 7
Does the monitored
input turn on and off?
NO
YES
NO
YES
YES
Call IDEC for assistance.
Monitor the designated stop or
reset input using WindLDR on a
computer.
NO
Is the designated stop or
reset input on?
Is M8000 off?
Turn on the designated input.
The input circuit in the CPU module
is damaged.
Replace the CPU module.
Is stop or
reset input designated in
the WindLDR Function Area
Settings?
Monitor the start control special
internal relay M8000 using WindLDR
on a computer.
YES
Turn off the start control special
internal relay M8000 using WindLDR
on a computer.
NO
Cannot stop or reset operation.
Note:
To monitor M8000, from the WindLDR menu bar, select
Online > Monitor > Monitor, then Online > Custom > New Cus-
tom Monitor. Enter M8000 in the Device box in the Custom
Monitor dialog box.
Note:
To turn off M8000, enter 0 in the Current Value box in the
Custom Monitor dialog box.